Help Center · PowerSense

Troubleshooting

Overloaded lists that looked fine, cable verdicts that will not clear, neutral warnings, missing gear on another device, and a blocked print window.

Open PowerSense

Symptom Likely cause & fix
A list is Overloaded although the total looks small One phase carries most of the load. Press Auto-balance phases, or move hand-assigned devices to a lighter phase.
Headroom turned amber Worst-phase headroom is under 20 %. Raise the feed, move gear to another list or accept that this distro is tight.
A generator list turns amber or red earlier than a mains list Intended. Generator feeds warn from 70 % continuous load and turn red from 90 %, and they are also compared with the engine's kW.
North America: flagged at 85 % of the breaker Intended. The NEC does not allow more than 80 % of a breaker for continuous loads.
A hoist or 400 V rack made the per-phase current jump Correct behaviour since v2.13: an amp-plated 3-ph device loads every phase in full. Earlier plans under-read by 3×; re-check old plans.
A device sits on the wrong phase after adding gear The plan was not pinned, so auto-balance reshuffled it. Press Pin auto phases once the layout is right.
Cable verdict Undersized for its breaker The breaker in Protected by is bigger than the cable's rating. Use a bigger cross-section, or set Protected by to the breaker actually in front of this run.
Cable verdict Undersized — exceeds cable rating will not clear The run takes the worst-phase current by default, and a drum, bundling or a hot day lowers the rating. Go up a gauge, unroll the drum, or type the current if this run really carries only a sub-load.
Voltage drop above 5 % on a long run Shorten the run or increase the cross-section. Check that System matches the cable: a 1-phase run has about twice the drop of a balanced 3-phase one.
The drop went up after an update Since September 2026 PowerSense takes copper at operating temperature and computes 1-phase and uneven runs on the loaded phase. The old figures read low.
A neutral-current warning appears The list is marked mostly LED / switch-mode. Keep it; tell the electrician. See Check cable runs.
Feed above the preset range Breaker size is beyond the rule-of-thumb table. Have the electrician engineer the feeder; the tool will not guess.
My gear or a list is missing on another device Both devices must be signed in to the same account and online. Reload the page. See Account sync.
Account sync is paused — reload the page to reconnect The sync connection dropped. Changes are saved on this device; reload when you have signal.
Local saving is unavailable in this browser Private mode or full storage. Use a normal window; account sync is the only safety net until then.
Print window was blocked Allow pop-ups for this site and print again.
CSV opens in one column The file is semicolon-separated. Use your spreadsheet's import dialog and choose ; as the delimiter.
A preset device's wattage looks wrong for my unit Presets are typical values. Edit the power in the row to the nameplate — and consider the safety margin for inrush.

When the numbers disagree with the electrician

The electrician is right. PowerSense compares your list with guideline values; it does not see earthing, loop impedance, RCDs, how the cables are laid or anything measured on site. Use the plan to arrive prepared; the qualified person on site makes the final call.