Check cable runs

Add a run, let it take the worst-phase current, and read the rating and voltage-drop verdicts — plus the feeder rule of thumb.

PowerSense öffnen

Diese Seite gibt es bisher nur auf Englisch.

Auf dieser Seite
  1. Add and configure a run
  2. Read the verdicts
  3. How the drop is calculated
  4. The feeder rule of thumb

A distro that "has room" still trips when the cable to it is too thin or too long. PowerSense checks each run twice: against a conservative current rating for its cross-section, and for voltage drop over its length.

Add and configure a run

  1. In Cable runs, press + Add run. Each list starts with one run called Feed.
  2. Give it a Label (for example Feed → stage-left distro).
  3. Current (A) defaults to auto: worst phase — the highest phase current of this list, after the safety margin. Switch to manual to type a value for a sub-run that carries only part of the load.
  4. Enter the Length — metres in Europe mode, feet in North America mode.
  5. Choose the Cross-section (mm²) or AWG gauge.
  6. Set System to 1-phase or 3-phase to match the cable.

Read the verdicts

Verdict Meaning
OK Current is within the guideline rating and the drop is under 3 %.
Undersized — exceeds cable rating The run carries more than the rating for that gauge. Go up a size.
Voltage drop above 3 % — consider a bigger gauge Legal-ish but wasteful; long runs and amp racks will notice.
Voltage drop above 5 % Fail. Shorten the run or increase the cross-section.

The rating tables the verdicts use are shown under the check — the same numbers, nothing hidden. In Europe mode they run from 1.5 mm² (16 A) to 35 mm² (100 A); in North America mode from AWG 14 (15 A) to AWG 2 (95 A). They are guideline values for flexible rubber cable (H07RN-F / SOOW) in free air.

How the drop is calculated

The help dialog states the formulas the tool uses:

  • Single-phase: ΔU = 2 · ρ · L · I ÷ A
  • Three-phase: ΔU = √3 · ρ · L · I ÷ A
  • ρ = 0.0175 Ω·mm²/m (copper)

Warn above 3 %, fail above 5 % of the system voltage.

The feeder rule of thumb

Under the runs, a hint reads Feed rule of thumb: X A per phase → min Y. It is derived from the same table, so the hint can never recommend a gauge the cable check would call undersized. Above the preset range it reads Feed above the preset range — have the electrician engineer the feeder. That is not a limitation to work around; it is the point where a professional designs the feeder.

Ratings assume free air. Unroll drums fully under load and derate bundled or hot runs — the good-practice list says so, and the tool cannot see how your cable is laid. The final distro is signed off by a qualified electrician.